The LON I/O module with 2 analog inputs, 2 analog outputs and 2 digital outputs. It is suitable for controlling, for example, motorized vent valves and switching on alarm at the set threshold value. The inputs and outputs are scanned and activated by SNVT network variables. The analog inputs can be scanned simultaneously. The analog outputs can be activated proportionally, or previously defined voltage values can be adjusted. Both digital outputs can be activated individually or as a function of an adjustable threshold value. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.
- Connection with screw type terminal blocks
Resources
Specifications
General Data Protocol | TP/FT-10, free topology |
Neuron | FT5000 |
Transmission rate | 78 KBit/s |
Operating voltage | 24 V AC/DC +/- 10 % (SELV) |
Current consumption | 95 mA (AC) / 35 mA (DC) |
Relative duty cycle | 100 % |
Inputs | 2 x analog |
Input / voltage | 0 V to 10 V DC |
Input / resolution | 10 mV (0 to 100 %) |
Outputs | 2 x analog |
Output / voltage | 0 V to 10 V DC |
Output / current | 5 mA at 10 V DC |
Output / resolution | 10 mV (0 to 100 %) |
Output | 2 x digital |
Output / contacts | 2 NO (DPST-NO) photoMOS relay |
Switching voltage | max. 40 V AC/DC |
Continuous current | max. 100 mA |
Operation and bus display | Green and yellow LED |
Dimensions (W x H x D) | 35 x 69.3 x 60 mm |
Weight | 82 g |
Operating temperature range | -5 °C to 55 °C |
Storage temperature range | -20 °C to 70 °C |
Ingress protection for housing / terminal blocks | IP40 / IP20 |