Description
Male Plug | NEMA L21-30 |
Female Connector | NEMA L6-30 |
Leg Count | 3 |
Leg Length | 24 Inch |
Voltage | 208 Volts |
Amperage | 30 Amps |
Cable Length | 3.0 Meter / 10 Feet |
Tolerance | ± 50 mm / ± 2 inches for molded cords ± 100 mm / ± 4 inches for mechanical cords |
Conductor Count | 5 wires |
Color | Black |
Testing | Each cord is tested for dielectric voltage-withstand (Hi-Pot), polarization and continuity. |
Certification(s) | US & Canada - cULus |
Packaging | Loose & Bundled |
Weight | 8.2 lbs |
Product Reviews
-
Wiring not as expected
The L6-30 outlets are not wired line to neutral for each of the three phases, they are connected line to line. Not sure why the inlet cable is a 5 wire cable as the neutral is not connected anywhere??? ACA Response: These are L6-30 208V breakouts from a 3-phase L21-30 plug. Line to neutral (W) would result in only a 120V output. Each breakout uses a different pair of the 3 lines (X, Y, Z) to balance the load. We will be adding a cord drawing for this product to clarify its wiring.