Sold Out
Metz Connect

Metz Connect 11089313. BMT-Multi I/O BACnet MS/TP

No reviews yet Write a Review
$0.00
Metz Connect 11089313 BMT-Multi I/O BACnet MS/TP | American Cable Assemblies
Metz Connect 11089313. BMT-Multi I/O BACnet MS/TP
Metz Connect 11089313. BMT-Multi I/O BACnet MS/TP
Metz Connect 11089313. BMT-Multi I/O BACnet MS/TP
SKU:
MTZ11089313
UPC:
4.25E+12
Availability:
Call for pricing and availability
Minimum Purchase:
1 unit
Current Stock:
I/O type:
Mix I/O
Operating voltage:
24 V AC/DC
Connection type:
Screw type terminal blocks
Mounting style:
Standard rail TH35
Manual control facility:
yes
RoHS:
compliant
EAN:
4251394600901

Frequently Bought Together:

Inc. Tax
Ex. Tax

Description

The BACnet module BMT-Multi I/0 is a compact and rapidly to install solution to connect digital and analog signals from the actor and sensor level directly to a control unit in building automation via BACnet MS/TP protocol. 29 I/Os, some of them are configurable, are available for different tasks. The inputs and outputs can be controlled and scanned by standard objects via a BACnet Client. Module address and bit rate are set with two rotary switches on the front or by software. The relays K1 to K4 are equipped with a manual control and allow manual intervention. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

Resources

BMT-Multi I/O BACnet MS/TP | 11089313View DataSheet
BMT-Multi I/O BACnet MS/TP | 11089313View Product Information

Specifications

General Data
Protocol BACnet MS/TP
Address range 00 to F9 hex
Bus interface RS485 (two-wire bus)
Transmission rate 9600 to 115200 bit/s
Operating voltage 24 V AC/DC / +/- 10% (SELV)
Current consumption 220 mA (AC) / 110 mA (DC)
Relative duty cycle 100 %
Inputs / digital 11 x optocoupler,galvanically isolated
Input / S0 1 x per DIN EN 62053-31, Class A
Inputs analog configurable
for resistance or 6 x 40 Ohm to 4 MOhm
for voltage 6 x 0 to 10 V DC
Input / current 1 x analog 0 to 20 mA DC
Outputs / Relay 4 x changeover (4PDT) / 250 V AC / 6 A
Manual control push buttons, shift fromautomatic to manual operationby pressing > 1 s
Outputs / PhotoMOS 4 x 24 V DC / 100 mAgalvanically isolated
Outputs / voltage 2 x analog 0 to 10 V DC / 5 mA,galvanically isolated