The BACnet MS/TP with 4 analog inputs was developed for decentralized switching tasks. It is suitable for detecting currents and voltages of, for example, active temperature sensors, electrical vent and mixing valves, valve positions, etc. Each input can be set as current or voltage input by DIP switches on the front. The inputs can be scanned with standard objects via a BACnet client. Module address and bit rate are set with the two rotary switches on the front. Suitable for decentralized mounting on TH35 rails according to IEC 60715 in electrical distribution cabinets.
- Connection with screw type terminal blocks
Resources
Specifications
General Data Protocol | BACnet MS/TP |
Addressing range | 00 to F9 |
Bus interface | RS485 (two-wire bus) |
Transmission rate | 9600 to 115200 bit/s |
Operating voltage | 24 V AC/DC +/- 10 % (SELV) |
Current consumption | 25 mA (AC) / 10 mA (DC) |
Relative duty cycle | 100 % |
Inputs | 4 x analog |
Input / voltage | 0 V to 10 V DC |
Input / resolution | 1 mV (0 to 100 %) |
Input / error | 10 mV |
Input / current | 0 (4) to 20 mA DC |
Input / resolution | 2 µA |
Input / error | 20 µA |
Display | Green and red LED |
Dimensions (W x H x D) | 35 x 69,3 x 60 mm |
Weight | 95 g |
Operating temperature range | -5 °C to 55 °C |
Storage temperature range | -20 °C to 70 °C |
Ingress protection for housing / terminal blocks | IP40 / IP20 |