The BACnet MS/TP module in IP65 housing with 4 digital inputs and 2 relay outputs with manual control was developed for decentralized switching tasks. It is suitable for accommodating, for example, light switches and window contacts in a room, switching two light strips or controlling louvers. It can also be used to control 2 motorized fire dampers. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. The inputs can be used as contact or voltage inputs. The inputs and outputs can be switched and scanned by means of standard objects via a BACnet client. Module address and bit rate are set with two rotary switches.
Resources
Specifications
General Data Protocol | BACnet MS/TP |
Addressing range | 00 to F9 |
Bus interface | RS485 (two-wire bus) |
Transmission rate | 9600 to 115200 bits/s |
Operating voltage range | 230 V +/- 10 % |
Current consumption | 200 mA (AC) / 12 mA (DC) |
Relative duty cycle | 100 % |
Inputs | 4 x digital (contact) |
Output / contacts | 2 changeover contacts (DPST) |
Output / switching voltage | 250 V AC |
Output / continuous current (UL) | 8 A / output |
Output / continuous current (VDE) | 10 A / output |
Display | Green, red and yellow LED |
Dimensions (W x H x D) | 159 x 41.5 x 120 mm |
Weight | 350 g |
Operating temperature range | -5 °C to 55 °C |
Storage temperature range | -20 °C to 70 °C |
Ingress protection for housing / terminal blocks | IP65 / IP20 |