The BACnet MS/TP module with 4 digital triac outputs was developed for decentralized switching tasks. It is suitable for switching electrical components, such as relays, contactors, HLK valves, etc. The outputs can be switched by means of standard objects via a BACnet client. In addition, the outputs can be overridden manually by means of switches on the device. The module is addressed and the baud rate is set by means of two address switches on the front. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.
- Connection with spring clamp terminal blocks (push-in)
Resources
Specifications
General Data Protocol | BACnet MS/TP |
Addressing range | 00 to F9 |
Bus interface | RS485 (two-wire bus) |
Transmission rate | 9600 to 115200 bit/s |
Operating voltage | 24 V AC/DC +/- 10 % (SELV) |
Current consumption | 100 mA (AC) / 40 mA (DC) |
Relative duty cycle | 100 % |
Output / contacts | 4 digital outputs (triac) |
Output / switching voltage | 24 V AC up to max. 250 V AC |
Output / continuous current | 0.5 A / output |
Output / switching current | 0.8 A (less than 30 s) |
Output / switch-on current | 10 A (less than 20 ms) |
Display | Green, red and yellow LED |
Dimensions (W x H x D) | 35 x 69.3 x 60 mm |
Weight | 95 g |
Operating temperature range | -5 °C to 55 °C |
Storage temperature range | -20 °C to 70 °C |
Ingress protection for housing / terminal blocks | IP40 / IP20 |