Sold Out
Metz Connect

Metz Connect 1108441370. MR-F-LD6 Modbus RTU

No reviews yet Write a Review
$0.00
Metz Connect 1108441370 MR-F-LD6 Modbus RTU | American Cable Assemblies
Metz Connect 1108441370. MR-F-LD6 Modbus RTU
Metz Connect 1108441370. MR-F-LD6 Modbus RTU
Metz Connect 1108441370. MR-F-LD6 Modbus RTU
Metz Connect 1108441370. MR-F-LD6 Modbus RTU
SKU:
MTZ1108441370
UPC:
4.25E+12
Availability:
Call for pricing and availability
Minimum Purchase:
1 unit
Current Stock:
I/O type:
Mix I/O
Functions:
Level/leakage monitoring
Operating voltage:
24 V AC/DC
Connection type:
Spring clamp terminal blocks
Mounting style:
Standard rail TH35
RoHS:
compliant
EAN:
4251394620725

Frequently Bought Together:

Inc. Tax
Ex. Tax

Description

The Modbus module with 6 analog inputs and 2 relay outputs was developed for decentralized switching tasks. Suitable to monitor electrodes of leakage sensors or the fill level of fluid containers and to switch pumps or magnetic valves. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. The resistance of the conductive fluid is measured when the electrodes are immersed. It is also possible to signal a cable break (requires sensor LKS-ZD). The module can be operated independently or via a Modbus master. Inputs and outputs can be switched and scanned via standard registers. Module address, bit rate and parity are set with two rotary switches on the front or by software. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

  • Connection with spring clamp terminal blocks (push-in)

Resources

MR-F-LD6 Modbus RTU | 1108441370View DataSheet

Specifications

General Data
Protocol Modbus RTU
Address range 00 to F9
Bus interface RS485 (two-wire bus)
Transmission rate 1200 to 115200 bit/s
Operating voltage 24 V AC/DC +/- 10 % (SELV)
Current consumption 80 mA (AC) / 43 mA (DC)
Relative duty cycle 100 %
Input / contacts 1 to 6 connection of the electrodes
Input / contacts C common reference potential
Internal resistance 20 kOhm
Sinus voltage 3 Veff, 70 Hz at resistance measurement
Measuring accuracy +/-10 % with sensor resistance 4 to 40 kOhm; +/-20 % with sensor resistance 2 to 100 kOhm
Pulse voltage +/-16 V at wire break monitoring
Zener diodes 6.2 to 10 V can be used as line termination
Lines capacity 40 nF max. equates 400 m at 100 nF/km
Measuring interval 1.5 s
Output / contacts 2 NO contacts (SPST-NO)
Output / switching voltage 250 V AC
Output / continuous current 6 A / output
Display Green, red and yellow LED
Dimensions (W x H x D) 50 x 69.3 x 60 mm
Weight 126 g
Operating temperature range -5 °C to 55 °C
Storage temperature range -20 °C to 70 °C
Ingress protection for housing / terminal blocks IP40 / IP20

Product Reviews

Discounts, Specials & New Products. Delivered Regularly.