The Modbus module with 4 digital inputs was developed for decentralized switching tasks. It is suitable for detecting potential-free switch states, for example electrical limit switches on vent valves or auxiliary contacts of power contactors. The inputs can be operated by means of potential-free switches or contacts or used as voltage inputs. The inputs can be scanned by means of standard registers via a Modbus master. Module address, bit rate and parity are set with 2 rotary switches on the front or by software. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.
                       -  Connection with screw type terminal blocks 
Resources
Specifications
               General Data               | Protocol | Modbus RTU | 
  | Address range | 00 to 99 | 
  | Bus interface | RS485 (two-wire bus) | 
  | Transmission rate | 1200 to 115200 bit/s | 
  | Operating voltage | 24 V AC/DC +/- 10 % (SELV) | 
  | Current consumption | 50 mA (AC) / 20 mA (DC) | 
  | Relative duty cycle | 100 % | 
  | Inputs | 4 x digital | 
  | Input / voltage | 30 V AC/DC | 
  | Input / high signal | more than 7 V AC/DC | 
  | Display | Green, red and yellow LED | 
  | Dimensions (W x H x D) | 35 x 69.3 x 60 mm | 
  | Weight | 95 g | 
  | Operating temperature range | -5 °C to 55 °C | 
  | Storage temperature range | -20 °C to 70 °C | 
  | Ingress protection for housing / terminal blocks | IP40 / IP20 |