The Modbus module with 4 digital inputs and 2 relay outputs with manual control was developed for decentralized switching tasks. It is suitable for accommodating, for example, light switches and window contacts in a room, switching 2 light strips or controlling louvers. It can also be used to control 2 motorized fire dampers. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. The inputs can be used as contact or voltage inputs. The inputs and outputs can be switched and scanned by means of standard registers via a Modbus master. Module address, bit rate and parity are set with 2 rotary switches on the front or by software. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.
- Connection with screw type terminal blocks
Resources
Specifications
General Data Protocol | Modbus RTU |
Address range | 00 to 99 |
Bus interface | RS485 (two-wire bus) |
Transmission rate | 1200 to 115200 bit/s |
Operating voltage | 24 V AC/DC +/- 10 % (SELV) |
Current consumption | 200 mA (AC) / 75 mA (DC) |
Relative duty cycle | 100 % |
Inputs | 4 x digital |
Input / voltage | 30 V AC/DC |
Input / high signal | more than 7 V AC/DC |
Output / contacts | 2 changeover contacts (DPDT) |
Output / switching voltage | 250 V AC |
Output / continuous current | 16 A / output |
Output / switch-on current | 80 A, less than 20 ms |
Display | Green, red and yellow LED |
Dimensions (W x H x D) | 50 x 69.3 x 60 mm |
Weight | 126 g |
Operating temperature range | -5 °C to 55 °C |
Storage temperature range | -20 °C to 70 °C |
Ingress protection for housing / terminal blocks | IP40 / IP20 |