The Modbus module inan IP65 housing with 4 digital inputs and 2 relay outputs with manual control was developed for decentralized switching tasks. It is suitable for accommodating, for example, light switches and window contacts in a room, switching two light strips or controlling louvers. It can also be used to control 2 motorized fire dampers. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. The inputs have to be connected to potentialfree contacts. The inputs and outputs can be switched and scanned by means of standard registers via a Modbus master. Module address, bit rate and parity are set with two rotary switches. Bit rate and parity are also set by software.
Resources
Specifications
General Data Protocol | Modbus RTU |
Addressing range | 00 to 99 |
Transmission rate | 1200 to 115200 bit/s, Factory setting 19200 bit/s Even |
Bus interface | RS485 two wire bus with potential equalization in bus or line topology terminate with 120 Ohm |
Operating voltage | 230 V +/- 10 % |
Current consumption | 12 mA |
Relative duty cycle | 100 % |
Inputs | |
Digital inputs | 4 |
Voltage input | 30 V AC/DC |
High signal recognition | more than 8 V AC/DC |
Outputs | |
Output contacts | 2 changeover contacts (DPST) |
Switching voltage max. | 250 V AC |
Continuous current max. | 10 A per relay (65 A for 20 ms) max. current via terminal "11" 10 A |
Housing | |
Dimensions (W x H x D) | 160 x 40.7 x 120 mm |
Weight | 350 g |
Mounting position | any |
Mounting | directly on a flat surface 8 knock-out openings for M12 and M16 cable glands |
Operation | 23 °F to 131 °F (-5 °C to 55 °C) |
Storage | -4 °F to 158 °F (-20 °C to 70 °C) |
Type of protection (IEC 60529) | IP65 |
Display | |
Operating and bus activity | green LED |
Error indication | red LED |
Status of inputs and outputs | yellow LED's |