CAN module with 4 digital outputs. It is suitable for switching electrical components, for example motors, contactors, lamps, louvers, etc. With strong inductive loads, we recommend protecting the relay contacts additionally with an RC element. The fieldbus module is an input module for universal use. It is controlled by means of the CAN bus. The module is addressed by means of an adjustable address. Data bytes transmit whether data are queried or commands are executed. If there is a digital input module with the same address in the system, the module can be operated by remote control.
- Connection with screw type terminal blocks
Resources
Specifications
General Data Protocol | CAN |
Addressing range | 00 to 99 |
Bus interface ©CiA standard | 2.0B passive (two-wire bus) |
Transmission rate | 20 to 500 kBit/s |
Operating voltage | 24 V AC/DC +/- 10 % (SELV) |
Current consumption | 205 mA (AC) / 67 mA (DC) |
Relative duty cycle | 100 % |
Recovery time | 550 ms |
Output / contacts | 4 x changeover contacts (4 DPST) |
Output / switching voltage | 250 V AC |
Output / continuous current | 5 A / output |
Output / total current | max. 12 A / all outputs |
Display | Green, red and yellow LED |
Dimensions (W x H x D) | 35 x 69.3 x 60 mm |
Weight | 104 g |
Operating temperature range | -5 °C to 55 °C |
Storage temperature range | -20 °C to 70 °C |
Ingress protection for housing / terminal block | IP40 / IP20 |