Description
Features
- Used (with 150 Volt full scale A.C. voltmeters) to measure the voltage of 240, 480 or 600 VAC systems.
- Primary insulated for 4.0 KV rms test, suitable for L.V. switchgear and motor control use.
- 50/60 Hz. operation.
- Open construction - "Type H".
- CSA certified (209651).
- The nominal line voltages of 240 and 480 volts may be exceeded by 25% for 60 Hz. operation.
- Insulation system 55 degree C rise, Class 105.
Specifications
Nominal Line Voltage | 600 |
---|---|
Ratio Pri./Sec. | 600:120 |
Accuracy % | 1.2 |
VA | 0-20 |
Thermal Rating | 100 |
Drawing Sheet | Download Drawing Sheet |