Description
48 Strand, OCC DX Series, Outdoor Burial, CST Armored DX Distribution, Multimode 62.5/125
Reference Previous Part Number: DX48-105D-WLS/900-CST
Note: This item may require 24 hours for cut and prep before shipping.
Cable Charecteristics: D-Series Distribution Riser Cables
Tensile Load | Menimum Bend Radius | ||||||
Diameter | Weight | Installation | Operational | Installation | Long Term | ||
Fiber Count | Part Number | mm/(in) | kg/km (lbs/1,000) | N (lbs) | N (lbs) | cm (in) | cm (in) |
48 | DX048DWLS9KAA2 | 10.1 (0.40) | 93 (63) | 4,200 (940) | 1,400 (310) | 15.2 (6.0) | 10.1 (4.0) |
DISTRIBUTION SERIES FIBER OPTIC CABLE TYPE OFNR RISER PRODUCT SPECIFICATIONS
Applications
- Indoor/Outdoor tight-bound tight-buffered design allows cables to be installed in intra-building campus locations without costly transitions between cable types
- Ideal configuration for a single termination point reguiring multiple fibers
Features
- High performance components and construction
- Cable materials are Indoor/Outdoor UL-listed OFNR and UV, water and fungus resistant
- UL Listed in accordance with NEC section 770.179 (b) for use in vertical runs in building riser shafts or from floor to floor
- Wide operating temperature range of -40°C to +85°C
- Helically stranded core for greater flexibility and mechanical protection of the optical fibers
- High strength-to-weight ratio
- 2-144 fiber configuration is smaller and lighter than comparable sub-grouped cables, which is ideal for installation in areas with limited space or tight bends
- Can be armored for additional protection in direct burial and aerial installations
- Interlocking armor can be applied to cables as an alternative to conduit installation
Cost savings
- 900 µm buffer eliminates the need for costly and time-consuming installation of fanout kits or pigtail splices because connectors terminate directly to the fiber
- No need to splice Outdoor cable to Indoor cable at building entrance
- High crush resistance may eliminate the need for innerduct
Mechanical and Environmental Performance
Indoor/Outdoor | |
Operating Temperature | -40°C to +85°C |
Storage Temperature | -55°C to +85°C |
Installation Temperature (cable temp.) | -10°C to +60°C |
Flame Retardancy | UL Listed Type OFNR (UL 1666) and FT4 (CSA C22.2 No. 232) |
Impact Resistance | 1,500 impacts |
Crush Resistance | 1,800 N/cm |
Flex Resistance | 2,000 Cycles |
Note: These specifications are subject to change without prior notification.